Why do circuit breakers have two trip coils?

Why do circuit breakers have two trip coils?

To prevent flash-overs due to low gas, breakers are fitted with ANSI ’63’ relay. Tripping of breaker is cut out by this relay’s contact. Most modern circuit breakers are specified with two trip coils. Energizing either one trips the breaker.

What is the purpose of trip coil used in circuit?

Trip coils are the release components in circuit breakers used in energy distribution for the switching of high currents. It is their task to interrupt fault currents/voltages so that downstream systems are not damaged. The trip coil triggering solenoid initiates this separation mechanism.

What is the purpose of trip circuit supervision relay?

The trip circuit supervision relay SPER 1C1 is used for supervising important control circuits, such as, circuit-breaker and disconnector control circuits and signalling circuits in power electrical installations. Generally, one supervision relay is needed per circuit to be supervised.

What is the use of shunt trip coil in Mccb?

The shunt trip is used to disconnect the main power supply to the circuit it is connected within case an electrical signal is received. Whenever a shunt trip device receives a signal from the current transformer it is tripped.

What is the difference between tripping and closing coil?

Therefore, operating the closing latch requires greater force than for operating the tripping latch i.e. stronger magnetic field is required for closing than for tripping. Hence, closing coil resistance is designed much less than tripping coil resistance to have a stronger magnetic field.

What is trip coil monitoring?

A Trip Coil Monitor is either an input to a protective relay or a stand alone relay. It is meant to monitor the continuity or “health” of the tripping circuit to a circuit breaker or a lockout relay. A typical setup is shown in the circuit above.

What is trip circuit healthy indication?

The trip circuit supervision, in its simplest form, may consist of a ‘Trip Circuit Healthy (TCH)’ indication lamp, as shown in the figure below. To avoid any unwanted tripping of the breaker, in the event of any short circuit in the lamp, a series resistor (R) is added in the circuit.

Where are shunt trip breakers required?

Generally, most commercial kitchens, elevators, and offices have this shunt trip breaker because it is required. Commercial kitchens use this device in compliance with ANSI/ASME CSD-1, while elevators and escalators comply with ASME A17.

What is the difference between shunt trip and undervoltage trip?

The main difference between a shunt trip and an undervoltage release is that the shunt trip opens the circuit breaker when a control voltage is applied to its coil. On the other hand, the undervoltage release trips the breaker when a control voltage is removed from its coil.

How does trip circuit healthy work?

Trip Circuit Supervision Circuit senses any fault either in the trip coil of breaker or trip circuit. On sensing a fault, Trip Circuit Supervision Relay changes its contact status to window annunciation on the panel. Here fault in the circuit means any break or open circuit.

What is the normal part of trip circuit?

The trip circuit of a switchgear may include the main protection relay, the master trip relay, relay contacts, switchgear auxiliary contacts, fuses, links, wiring, terminal blocks etc. With so many components, the probability of the trip circuit becoming unhealthy is quite high.

Why would you need a shunt trip breaker?

A shunt trip breaker is an optional accessory for your circuit breaker that can allow you to trip the breaker remotely at any time or automatically during a surge, preventing injuries and equipment damage during emergencies.

What is a shunt trip?

A shunt trip device is an optional accessory in a circuit breaker that mechanically trips the breaker when power is applied to the shunt trip terminals. The power for the shunt trip does not come from within the breaker, so it must be supplied from an external source.

What is the main disadvantage of a shunt motor?

Shunt motor is a constant speed motor, it would be disadvantages where it’s necessary to operate under variable speed. For the same current input, its starting torque is not a high as that of a DC series motor.

How does a trip coil circuit work?

The trip coil comes into the circuit and trips the circuit breaker when the relay contact opens at fault. The circuit is shown in Figure 2. This scheme is similar to the one using relays but here a summation CT is used to summate the current of all the three phases, thereby minimising the requirement of three series trip coils to one.

How is a series trip coil kept shorted in a relay?

Here the series trip coil is normally kept shorted through the NC contacts of the series tripping relays. The trip coil comes into the circuit and trips the circuit breaker when the relay contact opens at fault. The circuit is shown in Figure 2.

How to monitor the healtiness of circuit breaker trip coil circuit?

The healtiness of circuit breaker trip coil circuit is monitored by the trip circuit supervision relay TCS which monitors the circuit in open and close circuit breaker position (ANSI 74TC). In normal operation TCS supervision relay is always energised.

How does a 52B trip coil work?

With the 52a contact in the trip circuit (as shown in the scheme above), once the breaker opens, this contact opens too. Now no matter what the relays do, the trip coil is isolated. On the flip side, with the breaker open, the 52b contact in the close circuit is closed – allowing the close operation when desired.